Tellus Power Green DC Fast Charger
| Product # | HPC-240-480 |
| Model # | TP-EVPD-240kW |
| Maximum Power | 240 kW |
| Output Voltage | 150 – 1000 VDC |
| Max Output Current | Up to 500A |
| Input | 480V (3P + N + PE) || 60 Hz |
| Input Current || Breaker Rating | 320A || 400A |
| Power Factor | >0.98 |
| Efficiency | >94% at nominal output power |
| Connector Options | CCS1 and CCS1 CCS1 and NACS NACS and NACS CCS1 and CHAdeMO |
| CCS / NACS Cable | 500A Liquid Cooled |
| CHAdeMO Cable | 125A (Standard) Or 200A |
| Charging Protocol Standards | Mode 4,IEC-61851,ISO-15118,DIN 70121 || Mode 4, CHAdeMO 0.9,1.0 |
| Connector cable length | CCS / NACS - 13 ft (4 m) | CHAdeMO – 16ft (5 m) Cable Retractor Included |
| Weight | 1653 lbs (750 kg) |
| Dimensions (L x D x H) | 33.5‘’ x 33.9’’ x 81’’ |
| Insulation (input – output) | >2.5 kV |
| Ingress Protection | NEMA 3S (IP54), IK10 |
| Altitude | <6,600ft (2,000m) |
| Operating temperature | -30°C to 55°C (-22°F to 131°F ) |
| Working || Storage Humidity | ≤ 95% RH || ≤ 99% RH (Non-condensing) |
| Display | 10’’ touch screen |
| Communication Protocol | OCPP 1.6J |
| Access Control | RFID : ISO/IEC 14443A/B | Credit Card Reader (Optional) |
| Metering | DC kWh meter per each connector |
| Power Electronics Cooling | Air Cooled |
| Regulatory Compliance | UL-2202 || EMC: EN 61000-6-1:2007, EN 61000-6- 3:2007/A1:2011/AC:2012 |
| Electrical Safety: GFCI | RCD 20 mA Type A |
| Electrical Safety: Surge Protection | 20 kA |
| Electrical Safety General | Over Voltage, Under Voltage, Over Current, Missing Ground |
| Electrical Safety: Output Short | Output power disabled when output is short circuited |
| Electrical Safety Temperature | Temperature Sensors @ Charge Coupler and Power Electronics |
| Emergency Stop | Disables output power with emergency stop button |